Operating and functions
8.6.8. Configuring the transistor output DO1 to switch a load
depending on two threshold values
OUtPUt DO1 hYstEREs.
DO2
1-= 0.000
1+= 0.000
Enter a flow rate value
1)
, associated to the high
threshold, in the unit chosen in the "UNIT" parameter.
Confirm.
wiNDOw
Enter a flow rate value
1)
, associated to the low
threshold, in the unit chosen in the "UNIT" parameter.
Confirm.
iNV YEs
iNV NO
0......9
Choose the operating, inverted or not inverted, of the
transistor output.
DEL. 1= 00
Enter the time delay before switching value (value
between 0 and 99 s).
Confirm.
REtURN
On a version WITH relay out-
puts
On a version WITHOUT relay
outputs
1)
If hysteresis operating: value set for 1- value set for 1+. If window switching: value set for 1- < value set for
1+.
Fig. 35: Configuration of the DO1 transistor output with switching thresholds