23
Installation and commissioning
Power supply
Valve, pump,... (or metallic earthing rings, not supplied,
inserted within the pipe)
Power cable shield
+
-
18-36VDC
1)
Pipe in plastic
1
If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and
the earth.
Fig. 13: Equipotentiality skeleton diagram with pipes in plastic
Metal pipe
Power supply
Power cable shield
1)
+
-
18-36VDC
1
If a direct earth connection is not possible, fit a 100 nF / 50 V capacitor between the negative power supply terminal and
the earth.
Fig. 14: Equipotentiality skeleton diagram with pipes in metal
7.3.2. Mounting the cable clamp
Before wiring the device, insert the supplied cable clamp into the
notches of the electronic board.
Fig. 15: Mountign the cable clamp