Burkert Type 8045 Instrukcja Użytkownika Strona 13

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 98
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 12
13
Installation and wiring
Type 8045
Horizontal mounting
Correct Incorrect
Vertical mounting
Correct Incorrect
flow direction
Fig. 6: Filling of the pipe
- Prevent the formation of air bubbles in the pipe in the section
around the device (see Fig. 7).
- Always mount the device upstream a possible injection point
in the pipe of a high-conductivity fluid (for example: acid, base,
saline,...).
Respect the following additional mounting conditions to ensure
that the measuring device operates correctly:
- Preferably install the device at a 45° angle to the horizontal centre of
the pipe to avoid having deposits on the electrodes and false meas-
urements due to air bubbles (see Fig. 5);
45°
45°
Fig. 5: Mounting angle on the pipe
- Ensure that the pipe is always filled in the section around the
device (see Fig. 6).
- When mounting vertically ensure that the flow direction is in an
upward direction (see Fig. 6).
English
Przeglądanie stron 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 97 98

Komentarze do niniejszej Instrukcji

Brak uwag