Burkert Type 8625 Instrukcja Użytkownika Strona 32

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 118
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 31
30 - 8625-2 Standard
english
From K
crit
and T
crit
, the controller parameters can then be calculated using the
following table.
Parameter setting according to Ziegler and Nichols:
The adjustment rules of Ziegler and Nichols have been determined for P members
with first order time increase and dead time. However, they apply only for
controllers with disturbance behaviour and not for those with command behaviour.
Controller type Parameter setting
PK
p
= 0,5 K
krit
-
PI K
p
= 0,45 K
krit
T
N
= 0,85 T
krit